Electrical measurements
on adjustable speed drives
Ten measurements that tell you a lot
Published with permission from Fluke
Most experienced motor technicians are well prepared to deal with traditional
three-phase motor failures that result from the effects of water, dust, grease,
failed bearings, misaligned motor shafts, or just plain old age. However, modern
electronically controlled motors, more commonly referred to as adjustable speed
drives, present a unique set of problems that can vex the most seasoned pro.
This application note describes the electrical measurements you need to make
during the installation and commissioning of a drive, as well as when diagnosing
bad components and other conditions that may lead to premature motor failure
in adjustable speed drives (ASDs).
There are many different ways to go about
troubleshooting an electrical circuit, and a good
troubleshooter will always find the problem—
eventually. The trick is to track down the problem
as quickly as possible, keeping downtime
to a minimum. The most efficient procedure for
troubleshooting is to begin looking at the motor,
and then systematically work back towards the
electrical source, looking for the most obvious
problems first. A lot of time and money can be
wasted replacing perfectly good parts when the
problem is nothing more than a loose connection.
Next, take care to make accurate measurements.
Nobody makes inaccurate measurements
on purpose of course, but it is easier to do than
you may think, especially when working in a
high energy, noisy environment like that of an
ASD.
- If possible, do not use grounded test instruments.
They can introduce noise into a measurement
where none existed before.
- Avoid touching instruments and probes while
taking the reading, as electrical noise can get
coupled through your hands which may also
affect the reading.
- Because of the high noise environment, when
making current measurements use either a
clamp meter designed for this environment or,
if using a scope, use a current clamp that puts
out 10 mV/ amp or 100 mV/amp. They provide
a better signal to noise ratio than
1 mV/amp clamps when making current measurements
less than 20 amps.
- If using a digital multimeter with a clamp
accessory always use a current transformer
milliamp output clamp as this connects to
the low impedance current input jacks of the
DMM and is much less susceptible to the noise
in the environment.
Finally, it is a good idea to document electrical
measurements at key test points in the circuit
when the system is functioning properly. If a
good drawing does not exist, make one. A simple
one-line or block diagram will do nicely. Write
down voltage and temperature measurements
at key test points. This will save a great deal of
time and head-scratching later.
Making safe measurements
Before making any electrical measurements, be
sure you understand how to make them safely.
No test instrument is completely safe if used
improperly, and you should be aware that many
test instruments on the market are not appropriate
for testing adjustable speed drives.
Safety ratings for electrical test equipment
The International Electrotechnical Commission
(IEC) is the primary independent organization
that defines safety standards for test equipment
manufacturers. The IEC 61010 second edition
standard for test equipment safety states two
basic parameters, a voltage rating and a measurement
category rating. The voltage rating is
the maximum continuous working voltage
the instrument is capable of measuring.
When the voltage rating is coupled with a category
rating, it can be confusing. The category
ratings depict the measurement environment
expected for a given category. The measurement
environment for adjustable speed drives is not
always simple and may vary from installation to
installation. Most all three-phase ASD installations
would be considered a CAT III measurement environment.
Single phase ASD installations would be
a CAT II environment. If you are working in both
environments, play it safe and use only CAT III
rated test instruments. What may not be readily
obvious from looking at the following table is the
difference between a 1000 V CAT II rated meter
and a 600 V CAT III rated meter. At first glance,
you might think the 1000 V CAT II meter is the
better choice because it has a higher working
voltage than the 600 V CAT III meter and it can
handle the same level of high voltage transient,
which is true. However, the 600 V CAT III meter
can safely handle six times the power as the
1000 V CAT II meter, should a transient cause a
fault within the meter.
Also, avoid meters that claim to be “designed
to meet” EN61010 specifications or that do not
carry the test certification of an independent
testing lab such as UL, CSA, VDE, TÜV or MSHA,
as they do not always meet the specifications for
which they claim to be designed. Always look
for independent certification of test instruments
for ASD measurements. Refer to the ABC’s of DMM
Safety from Fluke for additional information on
category ratings and making safe measurements.
| Overage Category |
Examples |
| CAT IV |
- Refers to the "origin of installation", i.e. where low-voltage connection is made to utility power;
- Electricity meters, primary overcurrent protection equipment.
- Outside the building and service entrance, service drop from the pole to building, run between the meter and panel.
- Overhead line to detached building, underground line to well pump.
|
| CAT III |
- Equipment in fixed installations, such as switchgear and three phase motors.
- Bus and feeder in industrial plants.
- Feeders and short branch circuits, distribution panel devices.
- Lighting systems in larger buildings.
- Appliance outlets with short connections to service entrance.
|
| CAT II |
- Appliance, portable tools, and other household and similar loads.
- Receptacle outlets and long branch circuits.
- Outlets at more than 10 meters (30 feet) from CAT III source.
- Outlets at more than 20 meters (60 feet) from CAT IV source.
|
| CAT I |
- Protected electronic equipment
- Equipment connected to source circuits in which measures are taken to limit transient voltages to an appropriately low level.
- Any high-voltage, low-energy source derived from a high-winding resistance transformer, such as the high-voltage section of a copier.
|
Table 1. Measurement environment examples
Overvoltage
Category |
Working Voltage
(dc or ac-rms to ground) |
Peak Impulse Transient
(20 repetitions) |
Test Source
(Ohm = V/A) |
| CAT I |
600V |
2500V |
30 ohm source |
| CAT I |
1000V |
4000V |
30 ohm source |
| CAT II |
600V |
4000V |
12 ohm source |
| CAT II |
1000V |
6000V |
12 ohm source |
| CAT III |
600V |
6000V |
2 ohm source |
| CAT III |
1000V |
8000V |
2 ohm source |
Table 2. Transient test values for overvoltage installation categories
MotorsMeasurement 1
Low voltage
Low voltage
This troubleshooting step should always be
done before you attempt any other measurement.
Periodic tightening of connections is often
required to maintain a low resistance connection
between conductors. Visually inspect all connection
points for looseness, corrosion, or conductive
paths to ground. Even if the visual inspection
looks okay, you should use at least one, or some
combination of the following methods for checking
the connections.
Voltage drops
Check for voltage drops across the various connections.
Compare with the other two phases.
Any significant variation between phases, or
more than two or three percent (depending
on motor current and supply voltage) at each
connection, should be suspect.
Temperature measurements
The Fluke 60 Series Infrared Thermometers are a
fast and easy way to check for bad connections.
Any significant increase in temperature at the
connection terminal will indicate a bad connection
or contact resistance due to infrared heat
loss. If the temperature of the terminal was not
previously recorded onto your system diagram,
compare with the other two phases.
Voltage measurements
As the voltage applied to the motor terminals
by the ASD is non-sinusoidal, the voltage readings
displayed by an analog meter, an average
responding digital multimeter (DMM) and a truerms
DMM will all be different.
Analog meters
Many troubleshooters prefer using an analog
meter because the coil in the meter movement
responds in the same way as the motor to the
low frequency component of the waveform and
not the high frequency switching component.
The analog meter should correspond closely to
the voltage displayed on the ASD housing if
one exists.
Analog meters read the average voltage of the
modulation frequency of the PWM drive. While
it’s true the analog meter displays a voltage
reading close to what the PWM drive is displaying
and the motor is responding, safety is a big
concern with the analog meters as they generally
don’t have any EN61010 safety rating.
Digital multimeters
Many DMMs will respond to the high frequency
component of the motor drive waveform and
will therefore give a higher reading. A true-rms
DMM will give an accurate reading of the heating
effect of the non-sinusoidal voltage applied
to the motor, but will not agree with the motor
controller’s output voltage reading. However,
it should be noted that even though the motor
is not responding to the higher frequencies in
terms of torque or work being done, high frequency
currents might be flowing outside of
the windings due to various capacitances in
other parts of the motor. The issue is bandwidth.
The Fluke 33 x Clamp Meters, 787 and 789
ProcessMeters,™ 43B Power Quality Analzyer
and 190 Series ScopeMeter® Test Tools will all
provide voltage readings similar to that of the
analog meter and ASD display.
MotorsMeasurement 2
Voltage and current unbalance
Voltage unbalance
Next measure the phase-to-phase voltage
between the three motor terminals for voltage
unbalance. Voltage unbalances of as little as
two percent can cause excessive heating due
to unbalanced currents in the stator windings
and loss of motor torque. However, some motor
installations are more forgiving towards unbalances
so be sure to check out the entire motor
system for other causes should an unbalance
exist. As the relative difference between phase
voltages is what is being measured, not absolute
voltages, a DMM will give more accurate readings
with better resolution than an analog meter.
Use the following procedure to calculate voltage
unbalance.
For example, voltages of 449, 470 and 462
give an average of 460. The maximum deviation
from the average voltage is 11, and percent
unbalance would be:
11
____ | x 100 = 2.39 % |
| 460 |
Possible causes of voltage unbalance are: one
of the phase drive circuits is only partially conducting,
or there is a voltage drop between the
ASD’s output and the motor terminal on one of
the phases due to a poor connection.
There are other concerns about the motor
terminal voltages with regard to distortion, but
they must be measured and viewed using an
oscilloscope and will be discussed later in this
application note.
Current unbalance
Motor current should be measured to ensure that
the continuous load rating on the motor’s nameplate
is not exceeded and that all three-phase
currents are balanced. If the measured load
current exceeds the nameplate rating, or the current
is unbalanced, the life of the motor will be
reduced by the resulting high operating temperature.
If the voltage unbalance is within acceptable
limits, then any excessive current unbalance
detected could indicate shorted motor windings
or one or the phases shorted to ground.
Generally, current unbalance for three-phase
motors should not exceed 10 percent. As the current measurement will be made in a
high energy, electrically noisy environment, be
sure the proper current clamp is used as well as
good measuring technique as discussed earlier
in this application note. To calculate current
imbalance, use the same formula as stated for
voltage but substitute current in amps. For example,
currents of 30, 35 and 30 amps would give
an average current of 31.7 amps. The maximum
deviation from the average current would be
3.3 amps with a current unbalance of 10.4 %.
PWM Drives — Measurement 3
Overvoltage reflections at the motor terminals
The trend with PWM drives has been to make
the rise time of the pulses as fast as possible to
reduce switching losses and increase the efficiency
of the drive. However, fast rise times
coupled with long cable lengths produce an
impedance mismatch between the cable and the
motor causing reflected waves, or “ringing” as
shown in Figure 3A.
 |
| Figure 3A. Reflected voltages (ringing). |
If the rise times are slow enough, or the cable
short enough, the reflected waves will not occur.
The main problem with this condition is that
ordinary motor winding insulation can break
down quickly. Additionally, higher than normal
shaft voltages can develop causing premature
failure of bearings and excessive common mode
noise (leakage currents) can interfere with low
voltage control signals and cause GFI circuits to
trip.
 |
| Figure 3B. Impact of rise time and cable length on magnitude of reflected voltages. |
The relationship between cable length, rise
time and the resultant increase in peak voltage is
illustrated in Figure 3B. The peak voltage at the
motor terminals will increase above the dc bus
voltage of the ASD as cable length increases and
the rise time of the ASD output pulse gets faster.
Overvoltage reflections —
troubleshooting
As mentioned earlier, fast rise times on the ASD
output pulses and long cable runs between the
ASD and the motor will cause overvoltage reflections
approaching double the dc bus voltage and
even higher. An oscilloscope is required to discover
the full extent of this problem, as seen in
figure 3C.
Figure 3C shows the ASD L-L voltage measurement
at the motor terminals with six feet of
cable, while Figure 3D shows the ASD L-L voltage
with 100 feet of cable. Notice the difference
in peak voltage measurements—about 210 volts.
Also notice that there is only 5 V rms difference
between the two waveforms (small digits on the
display). This means your voltmeter will not find
this problem.
 |  |
| Figure 3C. Normal PWM waveform. | Figure 3D. PWM waveform with reflected voltages. |
Very few scopes will trigger as nicely and
easily as the Fluke 123 ScopeMeter® Test Tool
did for the measurements in Figures 3C and 3D.
 |  |
| Figure 3E. Leading edge of normal PWM pulse. | Figure 3F. Leading edge of PWM pulse with
reflected voltage (ringing). |
For other scopes use the following procedure to
measure the extent of the overvoltages.
The signals in figures 3E and 3F were captured
by triggering on a single pulse using single
shot mode with cursors enabled to make the
peak voltage measurement along with rise time.
While this measurement requires more button
pressing and scope “know how,” the automated
rise time measurement may be worth the trouble.
Manually resetting the single shot trigger
periodically will give you a sampling of various
peak voltages for the different pulses. Also,
slowly raising the trigger voltage will give you
an idea of the maximum peak when the scope
stops triggering.
Assuming you have identified a true overvoltage,
or ringing problem, then something must be
done about it. The simplest solution is to shorten
the cable. The peak overvoltages will continue to
increase to almost double the dc bus voltage as
the cable lengthens or rise time gets faster. The
peak voltages can even exceed voltage doubling
if the reflected voltage occurs on top of standing
waves due to the distributed inductance and
coupling capacitance of the cable.
The real danger of this overvoltage condition
is the damage it can do to the motor windings
over a period of time, which may not show up as
a problem when the PWM drive is first installed.
Many PWM drives are installed without taking
into consideration the overvoltage effects of long
cabling between the PWM output and the motor.
And while improved efficiency of the newest and
latest PWM drives are achieved by making the
rise times faster on the output pulses, this can
make the overvoltage problem even worse, and
the need for shorter cabling even greater.
If your motor has already failed and has to be
rebuilt, better insulated wire such as Thermaleze
Qs, or TZ Qs (by Phelps-Dodge), should be used
to rewind the motor. The main advantage is that
it provides significantly more protection against
overvoltages without adding insulation thickness
and the same stator can be used without modification.
If the motor has been damaged beyond
repair then a motor designed to meet NEMA
MG-31 specifications (sustained VPeak = 1600
V and rise time 0.1 µs) should be used as a
replacement motor for PWM applications where
sustained overvoltages may be occurring.
If the cabling in your PWM application cannot
be shortened then use one of these three solutions
to fix the problem.
- An external “add-on” low pass filter can be
installed between the PWM output terminals
and the cable to the motor to slow the rise
time.
- Install an R-C impedance matching filter at
the motor terminals to minimize the overvoltages,
or ringing effect.
- In some applications, such as submersible
pumps or drilling machines, it isn’t possible
to access the motor terminals and other methods
of minimizing overvoltages are required.
One method is to apply series reactors
between the PWM output terminals and the
cable to the motor. While this is a fairly simple
solution, the reactors may be fairly large,
bulky and expensive for large horsepower
applications.
A qualified engineer should design all
the solutions suggested above for your specific application.
|
Safety noteReflective voltage phenomenon can mean peak voltages 2-3 times
the dc bus voltage. For 480 V line voltage, this means a dc bus
voltage of 648 V and possible peak overvoltages of 1300 V-2000 V
and possibly higher given +10 % line voltage variance. Therefore it
is recommended that the measurement at the motor terminals be
made with the highest rated probe available and for the shortest
time possible where reflected voltages are likely to be present.
 |
Inverter Output Filter
Remedy 1 |
Series Reactor Motor
Remedy 2 |
Terminal Filter
Remedy 3 |
| Series connected to the PWM output terminals. |
Series connected to the PWM output terminals. |
Parallel connected at the motor terminals. |
| Designed to slow rise time (dv/dt) below a critical value. |
Acts as a current limiter and also slows rise time. |
Designed to match the characteristic cable impedance. |
| Dependent on cable length. |
Dependent on size of system. |
Not cable length dependent. |
| Losses dependent on motor kVA. |
Losses dependent on motor kVA. |
Losses are more or less fixed. |
| Size/cost dependent on motor kVA. |
Size/cost dependent on motor kVA. |
Size/cost more or less fixed. |
|
|
PWM Drives — Measurement 4
Motor shaft voltages
Bearing currents
When motor shaft voltages exceed the insulating
capability of the bearing grease, flashover
currents to the outer bearing will occur, thereby
causing pitting and grooving to the bearing races.
The first signs of this problem will be noise and
overheating as the bearings begin to lose their
original shape and metal fragments mix with the
grease and increase bearing friction. This can
lead to bearing destruction within a few months
of ASD operation—an expensive problem both in
terms of motor repair and downtime.
There is a normal, unavoidable shaft voltage
created from the stator winding to the rotor shaft
due to small dissymmetries of the magnetic field
in the air gap. This is inherent in the design of
the motor. Most induction motors are designed to
have a maximum shaft voltage to frame ground of
< 1 Vrms.
Another source of motor shaft voltages are
from internal electrostatic coupled sources including:
belt driven couplings, ionized air passing
over rotor fan blades, or high velocity air passing
over rotor fan blades such as in steam turbines.
Under 60 Hz sine wave operation, the bearing
breakdown voltage is approximately 0.4 to 0.7
volts. However, with the fast edges of the transient
voltages found with PWM drives, the breakdown
of the insulating capacity of the grease
actually occurs at a higher voltage—about 8 to
15 volts. This higher breakdown voltage creates
higher bearing flashover currents, which causes
increased damage to the bearings in a shorter
amount of time.
Research in this area has shown that shaft
voltages below 0.3 volts are safe and would not
be high enough for destructive bearing currents
to occur. However, voltages from 0.5 to 1.0 volts
may cause harmful bearing currents (> 3 A) and
shaft voltages (> 2 V) may destroy the bearing.
Care must be taken when making this measurement.
While the common is connected to the
motor frame ground, connect the probe tip to a
piece of twisted strand wire or a carbon brush
which in turn makes contact with the motor
shaft. As the shaft voltages are caused by fast
rise times of the PWM drive pulses, the voltages
will appear as narrow peaks. This measurement
is best made with an oscilloscope, not a
DMM. Even if the DMM has peak detect, there is
enough variation between peaks to render the
reading unreliable. Another measurement tip is
to make the shaft-to-frame ground voltage measurement
after the motor has warmed to its normal
operating temperature, as shaft voltages may
not even be present when the motor is cold.
The simplest solution to this problem is to
reduce the carrier (pulse) frequency to less than
10 kHz, or ideally around 4 kHz if possible. If the
carrier frequency is already in this range than
alternative solutions can be employed such as
shaft grounding devices or filtering between the ASD
and the motor.
PWM Drives — Measurement 5
Leakage currents (common mode noise)
Leakage currents
Leakage currents (common mode noise) capacitively
coupled between the stator winding and
frame ground will increase with PWM drives as
the capacitive reactance of the winding insulation
is reduced with the high frequency output
of the drive. Another leakage current path may
exist in the capacitance created when the motor
cables are placed in a grounded metal conduit.
Therefore, faster rise times and higher switching
frequencies will only make the problem worse.
It should also be noted the potential increase in
leakage currents should warrant close attention
to established and safe grounding practices for
the motor frame. The increase in leakage currents
can also cause nuisance tripping of ground
fault protection relays, override 4 to 20 mA
control signals, and interfere with PLC communications
lines.
Measure common mode noise by placing the
current clamp around all three motor conductors.
The resultant signal will be the leakage current.
A common mode choke can be used to reduce
leakage currents (see Figure 5A). Also, special
EMI suppression cables can be used between the
drive output and the motor terminals. The copper
conductors of the cable are covered with ferrite
granules, which absorb the RF energy and convert
it to heat. Isolation transformers on the ac
inputs will also reduce common mode noise.
 |
| Figure 5A. Common mode choke with dampening resistor to reduce leakage currents. |
PWM Drives — Measurement 6
Testing the IGBT output waveshape
PWM inverters
Many fractional horsepower PWM drives are
integrated to the point where the input diode
block and IGBTs are “potted” into a single throwaway
module that is bolted to the heat sink.
The cost of these units rarely justifies the time
to repair them and sometimes replacement parts
are not available. However, larger horsepower
drives starting in the 5 to 25 horsepower range,
have components that are accessible and the
cost of such drives makes repair an economically
viable alternative to replacement.
If it has been determined that the drive
inverter is the source of an improper voltagebeing applied to the motor, then use the following
procedure to isolate which IGBT(s) is failing
in the output section.
1. Check positive conducting IGBTs by connecting
the scope common lead to the dc+ bus
and measuring each of the three phases at the
inverter’s motor output terminals. Check for
nice, clean-edged square waves without any
visible noise inside the pulses, and that all
three phases have the same appearance.
2. Check negative conducting IGBTs by connecting
the common lead to the dc- bus and
performing the same measurements as in step
one above on each of the three phases at the
inverter’s motor output terminals.
 |  |
| Figure 6A. Square waves. | Figure 6B. Check all three phases at the inverter's motor input terminals. |
PWM Drives — Measurement 7
Testing the IGBT outputs for leakage
Check for “leaky” IGBTs by measuring the voltage
from earth ground to the inverter’s motor
output terminals with the drive powered on,
but the speed set to zero (motor stopped). Some
drives may have a normal earth ground to motor
PWM Drives — Measurement 7
Testing the IGBT outputs for leakage
terminal voltage of about 60 volts, with a reading
of over 200 volts indicating a leaky IGBT.
Perform this measurement on a known good
drive to determine what is normal for that drive.
PWM Drives — Measurement 8
ASD "trip" problems — overloading
If it is determined that the cause of overloading
is too much motor current, be sure that the
motor load is not causing the problem. Check for
excessive current unbalance indicating possible
shorted phase windings. Verify ASD trip points
are set correctly to the manufacturer’s specifications.
Finally verify that the dc bus voltage is
being regulated properly. Leaky capacitors
may cause excessive ripple and too little inrush current.
PWM Drives — Measurement 9
ASD "trip" problems — overvoltage
The dc bus
DC voltage too high
Transients (less than .5 cycle) and swells (.5
to 30 cycles) on the ac line inputs and motor
regeneration are the two most common causes
of “nuisance” tripping of the overvoltage fault
circuit on ASD inverters. Transients and swells
can be caused by events happening outside the
building like lightning or utilities switching KVAR
capacitors or transformer taps, as well as other
loads inside the building being switched on
(capacitive) or off (inductive). To test for these
situations, use an oscilloscope or power line
monitor with at least 10 µsec/ div. resolution,
and time-stamping capability.
The Fluke 43B Power Quality Analyzer is your
best choice for these measurements. The Fluke
ScopeMeter® 123 or 190 Series Test Tools are
also good choices for this measurement. Both
tools have plenty of single shot resolution and,
most importantly, can timestamp the event so it
can be correlated to whatever source—lightning,
utility or electrical equipment—is causing the
problem. Additionally, these tools are EN61010
600 V CAT III safety rated, an important consideration
when purposely measuring high magnitude
impulses in a high-energy environment.
If the drive is installed in a part of the country
that is prone to lightning activity, be sure
the building has proper surge protection that is
functioning properly. Additionally, the building’s
grounding system must be properly installed and
functioning to help dissipate lightning strikes
safely to earth, rather than through some path in
the building’s power distribution system. Steps
can and should be taken to minimize their effects
on your electrical and electronic equipment, since
a building that is susceptible to transients, sags
and swells, is usually a building that is deficient
in proper wiring and grounding.
If a transient voltage is
expected, then the 43B is an
excellent choice to measure
and, more importantly, time
stamp the transient so it can
time correlated to whatever
event caused the ASD fault.
If a transient causes the
tripping, then an isolation transformer
or series line reactor can
be placed in series with the
front end of the ASD. An alternate
solution would be to place
a surge protection device (SPD)
at the motor controlcenter, or the primary side of the distribution
transformer feeding the ASD. However, if the
source of the transient is coming from another
load on the same secondary feed as the ASD,
then a separate isolation transformer or series
line reactor may be needed directly in front of
the ASD. Better yet, put the ASD on its own feed.
 |
| Figure 9A. Overvoltage transient capture. |
Voltage swells > 30 cycles can be monitored
using the ScopeMeter TrendPlot™ mode or using
some other type of line monitor. One way to mitigate
the swell is to install a temporary dropout
relay for as many cycles as the swell, but that
can still be tolerated by the drive. The viability of
this solution will be determined by the amount
of “ride-through” the ASD’s input circuit can
handle before the dc bus voltage drops to an
under-voltage condition. Another possible solution
is to use a voltage regulation device like an
uninterruptible power supply (UPS), but it should
be noted that most UPSs are designed to handle
voltage sags and momentary interruptions and
may not handle voltage swell conditions unless
specifically designed to do so. Carefully check
the UPS manufacturer specifications.
Overvoltages or long-term voltage drift can
be caused by very large loads being turned off
within the building or a slow response of the
utility’s voltage regulation system to large reductions
in demand on the power grid. This condition
is easily discovered using the ScopeMeter
TrendPlot™ feature. The best way to deal with
this problem is to employ local voltage regulation
with a device like a UPS that is designed to
handle overvoltage as well as sags and dropouts.
Another common source for overvoltage on
the dc bus is motor regeneration. This occurs
when the motor load is “coasting” and begins
to spin the motor shaft rather than getting spun
by the motor, which causes the motor to change
into a voltage generator and returns energy to
the dc bus. Excessive regeneration can be measured
by checking for a change in the direction
of the dc current back into the dc bus while
simultaneously checking the dc bus voltage for
an increase above the trip point. When making
measurements on the ASD’s dc bus, choose
a CAT III 1000 V instrument. Typically a DMM
such as the Fluke 170 Series or the 87V is useful
because of their 1000 volt rating and min/max
recording capability. If regeneration is causing
the overvoltage tripping, something called
“dynamic braking” can be employed which limits
how fast the regenerative current is allowed to
feed back into the dc bus capacitors.
If the dynamic braking has already been
employed and is not functioning properly, then
it can be tested according to the manufacturer’s
specifications. If the brake is the resistor type, it
can be visually inspected for signs of overheating;
discoloration, cracking, or even smell for
that distinctive aroma of an overheated component.
The resistance value can also be measured
against the manufacturer’s specifications. If the
dynamic brake uses the transistor type, the silicon
junctions can be tested using a diode test as
described earlier. Also, the braking current can
be measured and the current waveform compared
with that of a known good system.
PWM Drives — Measurement 10
ASD "trip" problems — undervoltage
DC voltage too low
There are several possibilities for “nuisance”
tripping of the low voltage fault circuit on ASD
inverters. Voltage sags (.5 to 30 cycles) and
under voltages (> 30 cycles) on the line input
to the drive are common conditions associated
with this problem. Sags are quite often caused
by another load within the building’s distribution
system being turned on, or perhaps from a neighboring
building starting a large electrical load.
Make the measurement with an instrument
that can time stamp the sag or where the undervoltage
causes the ASD low voltage fault to trip.
You may want to start making this measurement
at the service entrance. This way you can
quickly isolate whether the sag is being caused
from within the building, or outside. Be sure to
monitor the voltage and current simultaneously.
That way you can tell whether the problem is
downstream from the service
entrance where the surge in current
is coincident with the voltage
sag. An upstream (outside
the building) problem would
show the voltage sag without a
corresponding surge in current. If
the problem is within the building,
there will be a current surge
coincident with the voltage sag.
Continue making the measurement
at different load centers
until you have isolated the load
with the corresponding voltage
sag and current surge.
 |
| Figure 10A. Voltage sag. |
Another possibility is a motor that is drawing
enough current to cause the dc bus voltage to
drop below the under-voltage fault setting, but
not enough to trip the current overload. You will
need to check the motor current for overloading
(compare with motor nameplate) as well as verify
whether the program settings of the drive are
correct for the motor nameplate ratings, including
the application for which the motor and drive
were intended.
 |
| Figure 10B. DC bus voltage drop below undervoltage fault setting |
Look at the line input voltage waveform to the
ASD. The wave-shape should be a nicely shaped
sine wave. Severe “flat-topping” of the waveform
can prevent the dc bus capacitors from fully
charging to the peak value, which lowers the
dc bus voltage as well as the amount of current
available to the ASD output circuit.
The top waveform in Figure 10C is taken from
a three-phase circuit. The current peaks of the
bottom waveform occur when the voltage waveform
is at or near its peak.
 |
| Figure 10C. Ideal line input voltage waveform. |
However, if the current peaks become larger
than the source can supply (i.e. source impedance
is too high for the load), you get flat topping
like the waveform shown here.
> |
| Figure 10C. Flat-topped waveforms |
Summary
In summary, while ASDs are more complex than
standard electrical motors, a systematic approach
to measurement and problem solving and the
right test tools can help significantly simplify their
installation, maintenance and troubleshooting.
While the 10 measurements described here by
no means cover everything you can know about
ASDs, they will provide you the information you
need for the majority of situations.
|
|